MASTERVOLTSnijdersbergweg 931105 AN AmsterdamThe NetherlandsTel.: +31-20-3422100Fax: +31-20-6971006http://www.mastervolt.comINSTALLATION MANUALV2. Oct
10 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENINSTALLATION2 "SUPER SILENT" EXHAUST SYSTEM In order to reduce the noise level of
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 11ABMax. length A - B = 3 m.ø 40 mmø 40 mmup to 3 m. ø 40 mm3-10 m. ø 50 mmFig. 9.Fig. 10.If the ge
12 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENINSTALLATION1.4.4 Digital Diesel Control system (12 Volt)1 DIGITAL DIESEL CONTROL SYSTEMThe elect
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 13Access to this menu and other menus could beblocked. For blocking and setting up this optio
14 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENINSTALLATION SPECIFICATIOINSVolt supply system, never take off 12 Volt (starting)power from
2 INSTALLATION SPECIFICATIONS2.1 WHISPER 6/8/12/6 ULTRA INSTALLATION TABLE1 Install a steel foundation plate between ship’s hulland generating
16 October 2004 / WHISPER 6/8/12 & 6 ULTRA / EN2.2 COMMISSION TABLE 1 Check if a siphon breaker (air vent) is necessary andhas been installed.2 O
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 17INSTALLATION SPECIFICATIONS2.3 INSTALLATION SPECIFICATIONS WHISPER 6/8/12 - 3000 RPM; 6 ULTRATECHN
INSTALLATION MATERIALS18 October 2004 / WHISPER 6/8/12 & 6 ULTRA / EN2.5 INSTALLATION MATERIALS WHISPER 6/8/12/6 ULTRAWATER INLET KIT 3/4”(20mm)no
INSTALLATION MATERIALSEN / WHISPER 6/8/12 & 6 ULTRA / October 2004 19FUEL KITno qtt articleno description dimensions41 2 50221203 Straight couplin
2 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENThis manual applies to the Mastervolt Whisper 6/8/12 and 6 ULTRA MarineDiesel Generating s
20 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENINSTALLATION MATERIALS- Fuel kit- Battery installation kit- Base plate kitWhisper 6/8/12/6 ULTRAInc
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 21INSTALLATION MATERIALS- Water inlet kit- Air vent kit- Exhaust kit-Water separator kitWhisper 6/8/1
22 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENDIAGRAMS& DRAWINGSJ20PUMPJ21ALTJ1ALTJ2REGULATORJ18 J19 J22START/STOPJ8 J9-J10-J11J12--J13--J14J
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 233.2 CODES AND COLORSCable code number colour cross sectionbattery > starter motor red 25 mm2sta
24 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENDIAGRAMS& DRAWINGS3.3 ELECTRONIC GOVERNOR (OPTIONAL)Fig. 16.
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 25ROTORSTATORPEN230V 50HzL1230V 50HzEARTH AND NEUTRAL CONNECTEDNPEL1EARTH AND NEUTRALNOT CONNECTEDMAI
26 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENDIAGRAMS& DRAWINGSThe remote panel comes in a carton that can be used asa template to drill the
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 27WHISPER 6/8WHISPER 12/6 ULTRAtopviewtopviewservice sideservice sideafb 18a.afb 18b.CONNECTIONS WHIS
MASTERVOLTSnijdersbergweg 93, 1105 AN Amsterdam, The NetherlandsTel.: +31-20-3422100 / Fax: +31-20-6971006www.mastervolt.com / [email protected]
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 31 INSTALLATIONTo ensure reliability and durability of the equipment, it isvery important that the i
4 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENINSTALLATIONAir inlets should be louvered, where appropriate, to pro-tect the engine room and t
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 52 FUEL LIFT PUMPThe generating set itself is equipped with a fuel liftpump; therefore the
6 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENINSTALLATIONWhen the tank is below the generating set we recom-mend to end the return line on the bo
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 71.4.2 CoolingIntercooling is based on a raw water pump, heat exchan-ger and water-injected exha
8 October 2004 / WHISPER 6/8/12 & 6 ULTRA / ENINSTALLATIONRestriction of raw water flow, caused by kinked hoses,undersized pipes or connections
EN / WHISPER 6/8/12 & 6 ULTRA / October 2004 9Check the air vent at regular intervals. Open, cleanand lubricate the valve as required.1.4.